How we handle lighting data
Keep the original values, make missing information visible and calculate only what the inputs support.
Your input stays distinct from verified evidence
Product entries, geometry conditions, operating assumptions and source links are supplied by you. The tools do not fetch a link, inspect a data sheet or verify a model. A declaration records your stated basis; it is not an approval.
Each calculation has its own conditions
- Luminaire efficacy divides matching whole-luminaire lumens by input watts, including required driver input, for the same model and setting. Lamp-only or unknown-level data is retained without an efficacy result.
- Beam geometry solves for diameter, full angle or axial distance in an ideal circular symmetric cone meeting an unobstructed perpendicular plane. The angle-defined circle is not an evenly lit area, a lux target or a spacing recommendation.
- Lighting energy and cost uses input power and duration over specified days. Simple mode compares one group per scenario; mixed-group mode sums non-overlapping daily states, including entered standby power and matching AUD/kWh tariffs. States for each group cannot exceed 24 hours per day. A missing rate leaves total cost unavailable while retaining valid energy. Fixed supply charges, demand charges and solar or battery effects are excluded. Comparing costs does not establish equivalent lighting service.
Missing, invalid and changed inputs
Each calculator opens with a labelled, editable artificial example and calculates it when its script is ready. Example values and selected conditions are for demonstration; replace them and check the conditions for your task, or use Clear all to start blank. Results update automatically as you edit, and invalid inputs remove the affected results. Blank fields are missing information, not zero. Each tool explains its supported ranges and required conditions beside the inputs. Energy accepts zero operating hours and a zero rate, while efficacy needs positive lumens and watts. An unknown rate leaves cost uncalculated without invalidating valid energy.
Precision and display
Calculations do not use display rounding in later steps. Efficacy uses at most two decimal places; geometric quantities and energy use two. Decimal energy and costs retain their entered precision, with monetary half-cents rounded away from zero only for display. Tiny nonzero results are identified with a less-than amount and their unit rather than shown as zero. Unrepresentable results are not returned as valid numbers.
Illuminance and power arithmetic
- Illuminance conversion uses the exact international-foot area: fc = lx × 0.09290304. Kilolux is lux divided by 1,000.
- Point-source illuminance uses directional candela × cosine of the incidence angle from the surface normal ÷ source-to-point distance squared. Multiple mode sums direct contributions at the same receiving point under the same conditions; it does not add a room-reflection model.
- Sample statistics use an arithmetic mean for equal-area readings or Σ(reading × represented area)/Σ(area) for supplied area weights. Readings must describe the same plane and conditions. Minimum/mean is undefined when every reading is zero; no measurement grid or standards threshold is supplied.
- Unadjusted lighting power density sums group count × whole-luminaire input watts, including required drivers, and divides by matching floor area. No NCC allowances or limits are applied.
Prepare geometry and maintenance inputs
Room index calculates rectangular area, luminaire-to-working-plane separation and K = LW/[h(L + W)] from a common height reference. It does not select utilisation data. The luminaire schedule sums matching group lumens and watts, with total lm divided by total W for aggregate efficacy. The maintenance-factor tool multiplies four supplied matching factors; no cleaning interval or factor is recommended.
Circular overlap calculates the intersection and union of two geometric discs. The rectangular grid divides a rectangle into equal cells and reports their centre coordinates and spacing-to-height ratios. Neither provides a lighting-performance contour, approved luminaire spacing or a standards measurement grid.
Declared light-distribution models
The lumen-method estimate multiplies matching initial complete-luminaire lm by count, a luminaire-based utilisation fraction and a maintenance fraction, then divides by working-plane area. Both fractions must be greater than zero and no more than one. Their basis must be recorded; no coefficient or room target is selected. Its reverse mode rounds the exact decimal count up before calculating the corresponding average. This average and arithmetic count do not define a layout or establish point illuminance or compliance.
The uniform-cone model uses Ω = 2π[1 − cos(θ/2)] sr and flux = constant cd × Ω, for full angles above 0° and no more than 180°. Flux displays to two decimal places and solid angle to four, calculated without intermediate display rounding. This is flux inside a circular cone with uniform intensity; a real beam angle and peak-candela rating do not establish that distribution or total lumens.
Simple payback model
Simple lighting payback divides additional upfront AUD by positive full-year net savings in AUD/year, assuming constant savings. It reports no positive payback for zero or negative savings, and identifies zero additional investment separately. The artificial example AUD1,200 ÷ AUD228/year equals 100/19 years, displayed as 5.26 years. This declared arithmetic model excludes discounting, financing, future price changes and replacement timing; it is not an investment recommendation.
Measurement and finite-source models
The meter specification range applies a supplied additive ±(% of reading + counts × resolution) form. Its nonnegative band is not a statistical confidence interval or a complete uncertainty budget. Daylight factor is 100 times paired indoor/outdoor illuminance under the declared overcast, simultaneous, unobstructed-reference and no-artificial-light conditions. A ratio above 100% is retained with a condition-check warning; no design target is supplied.
Diffuse reflected luminance uses L = Eρ/π only for a declared ideal Lambertian, non-emitting surface. The uniform disc model integrates E = πLr²/(r² + h²) at the on-axis point of a parallel receiving plane, for an unobstructed disc with uniform Lambertian luminance. These equations do not apply merely because a real surface or fitting looks diffuse or circular.
Cost plans, emissions and measured dimming data
Ownership cost adds supplied project upfront cost, constant-price energy, annual maintenance and planned replacement events over whole planning years. Replacements exactly at the horizon end are omitted. The comparison mode also discounts two options’ year-end costs at a supplied real annual rate, keeping upfront costs at time zero. The interval is a user plan, not a predicted failure time; financing, residual value and future price changes are excluded.
Operational emissions multiplies matching kWh by a user-supplied kg CO₂e/kWh factor and retains its stated location, year and accounting boundary. No Australian numerical factor is selected automatically. Dimming interpolation separately interpolates lm and W between matching supplied measurement points, then calculates lm/W where W is positive. It does not extrapolate or infer compatibility, and a control percentage is not assumed to be a power percentage.
Exposure budgets
Light exposure adds illuminance × duration in lx·h. An optional supplied budget gives remaining exposure and time at a stated future illuminance; exceeding the budget is shown separately. No material-specific budget, spectral damage model or preservation approval is supplied.
Photon plans, photographic settings and measured signals
The DLI planner integrates representative PPFD periods and plans an incremental supplement within a supplied daily window. Targets remain user-supplied. The schedule and sample tools have separate PPF/PPE and PPFD quantities; no universal lux-to-photon conversion is used. The photon-delivery budget is separate from photometric UF/MF.
Exposure and ND keeps absolute baseline and target filter losses distinct, with setting EV separated from unfiltered-scene equivalent EV100. Guide-number settings require compatible direct manual-flash ratings; multiple flashes add exposure contributions. Light ratios depend on whether the readings are separate contributions or measured totals. Mired shifts describe nominal reciprocal CCT, without predicting an arbitrary filter spectrum.
The waveform tool describes complete-cycle linear data with percent modulation and flicker index, without health or camera-banding thresholds. The spectrum workbench integrates declared linear nodes or constant bands, preserving absolute/relative scale and missing coverage. CIE 1931 2° observer data is attributed under CC BY-SA 4.0 on that page. No CRI, TM-30, CCT/Duv or biological response is calculated.
The reel planner allocates continuous cut runs to matching stock without splicing or assumed cutting loss. Its bounded search identifies whether a minimum new-reel count is proved; a feasible allocation alone is not labelled optimal. The tilted-cone mode in beam geometry requires half-angle plus axis tilt below 90° to form a finite ellipse.
Updates and corrections
Changes to calculation rules should be accompanied by independently checked examples and updated explanations.
What happens to your entries
Calculations run in your browser. They do not send entries to a server or store them in the URL or browser storage. Reloading starts a new calculation. The tool directory may preserve its search query in the URL. Following a source link takes you to that website under its own practices.