Unadjusted lighting power density divides the total electrical input of the included luminaires by the matching floor area: W/m² = Σ(count × input W each) ÷ area in m². It is an electrical-input measure. It does not say how much light reaches a desk, how evenly the room is lit or whether a fitting’s colour and glare characteristics suit the task.
Keep the power and area boundaries together. If the area is one room, include the luminaires serving that boundary on a consistent operating basis. Adding another room’s lights without adding its area inflates the result; adding unserved floor area reduces it without changing the lights.
YourHome’s lighting guidance distinguishes electrical power from light output and discusses integrated LED luminaires. For this arithmetic, use electrical input for the whole luminaire at the stated setting, including a required driver. LED-chip watts, nominal replacement watts and lumens are different figures.
Group lights only when their input watts match. Different fittings or settings need separate groups. For an artificial example, twelve luminaires at 18 W each total 216.00 W. Dividing by 36 m² gives 6.00 W/m².
Mixed groups can have the same total
Ten luminaires at 12 W plus two at 48 W also total 10 × 12 + 2 × 48 = 216 W. Over the same 36 m², the result remains 6.00 W/m². The identical density does not establish equivalent light output, distribution or operating cost.
The total uses unrounded inputs. Watts and W/m² display to two decimal places, with very small positive results identified rather than rounded to zero. Counts must be positive whole numbers and floor area must be greater than zero.
Why this is not an NCC assessment
A raw W/m² value is only one arithmetic quantity. An applicable NCC assessment can depend on building classification, adopted edition, jurisdiction, space definition and the relevant method’s allowances or adjustments. This tool applies none of those rules and has no maximum-value table or pass/fail output. Comparing its number to an unrelated limit would not establish compliance.
Operating time is a separate question. To turn a declared input power and operating schedule into energy, use the lighting energy and running cost calculator. A lower W/m² value alone cannot establish lower annual energy if operating hours change.