A control setting is not a measured light fraction
A setting of 40% identifies a control command. It does not by itself establish 40% of full lumens or 40% of full input watts. The luminaire, driver and control system determine the response, and YourHome’s lighting guidance discusses dimming and product suitability. This tool uses supplied measurements for that same system rather than assuming a universal response curve.
Each row pairs a setting with complete-luminaire output in lm and matching electrical input in W. Keep the driver, protocol, operating conditions and measurement basis consistent. At a zero setting, enter measured standby power if the system still draws it; zero control command does not prove zero electrical input.
For a setting x between two measured settings x₀ and x₁, let t = (x − x₀)/(x₁ − x₀). Apply linear interpolation to each quantity:
Lumens = (1 − t) × lm₀ + t × lm₁.
Watts = (1 − t) × W₀ + t × W₁.
Then divide the resulting lumens by watts to get lm/W when input power is positive. Interpolating endpoint efficacy instead would generally give a different answer because a ratio is not a linear sum. An exact supplied setting returns that measurement without interpolation.
Check an artificial midpoint
Take invented measurements of 200 lm at 3 W for setting 20%, and 800 lm at 8 W for setting 60%. At setting 40%, t = 20/40 = 0.5. The estimates are:
- Output: (200 + 800)/2 = 500.00 lm.
- Input: (3 + 8)/2 = 5.50 W.
- Efficacy: 500/5.5 = 90.91 lm/W.
The midpoint of the endpoint efficacies would be about 83.33 lm/W, which is not the efficacy of the interpolated output and input. Results display to two decimal places, using unrounded values in the ratio.
Stay within the measured range
Rows must have strictly increasing control settings. Repeated settings need investigation rather than an arbitrary choice between conflicting measurements. Settings outside the measured endpoints are rejected even when they fall within 0–100%. The nearest measured interval is used inside the range; additional measurements can reveal curvature that a long straight segment misses.
Piecewise interpolation does not guarantee the system follows those straight lines. It also does not assess flicker, colour shift, minimum stable output, dimmer compatibility or electrical suitability. At zero input W and zero lm, efficacy is undefined; positive light with zero input is rejected for this electrically powered luminaire model.
Carry the estimated input watts and its operating setting into energy calculations only as the same conditional estimate. Keep separate durations for different settings, and use product comparison to retain the system details needed to interpret them.