Keep each group’s light output and power together
A lighting schedule can contain different counts, lumen outputs and input powers. Summing one representative product from each row would lose the quantities. This calculator multiplies each group’s values by its count, then adds the groups:
Total lumens = Σ(count × initial complete-luminaire lm).
Total input watts = Σ(count × whole-luminaire input W).
YourHome’s lighting guidance distinguishes light output from input power and explains luminous efficacy in lm/W. Keep both values on the same complete-luminaire and operating-setting basis. Lamp-only output combined with power for a complete fitting can give a misleading efficacy. Required driver input belongs in the power figure.
The sum describes initial output from the luminaires. It does not describe the flux landing on a desk or the maintained illuminance of a room.
An artificial two-group schedule
Suppose one group contains four luminaires rated at 1,000 initial lm and 10 W each, and another contains two at 2,000 initial lm and 20 W each. The numbers are illustrative assumptions, not product recommendations.
The combined efficacy is 8,000 ÷ 80 = 100.00 lm/W. All totals use the entered decimals before display rounding. Count remains a whole number; lumens, watts and efficacy display to two decimal places.
Why the average of individual efficacies can be wrong
Imagine one 100 lm, 1 W light and one 900 lm, 3 W light. Their individual efficacies are 100 and 300 lm/W. Averaging those figures gives 200 lm/W, but the combined system produces 1,000 lm using 4 W: 250 lm/W. The larger power contribution must carry more weight. Dividing total output by total input does that directly.
Use the totals for the next task
The group counts and input watts can feed unadjusted lighting power density with a matching floor area. For energy and usage cost, each group also needs its operating hours and applicable tariff; one total wattage only represents all groups if their operating pattern is shared.
Do not divide total output by room area and treat the answer as actual illuminance. A declared-factor lumen-method estimate needs a compatible utilisation and maintenance model. Different luminaire types can have different distributions, so their flux totals do not establish one common UF or equivalent lighting service.
Compare photon output on a separate basis
For horticultural luminaires, select the PPF quantity and use 400–700 nm photosynthetic photon flux in µmol/s for each complete luminaire. DLC’s horticultural requirements distinguish total PPF from the quantity reaching a specific point, and define photon efficacy in µmol/J. Its North American qualification limits are not Australian requirements and are not applied here.
The group calculation remains Σ(count × PPF) and Σ(count × input W). Since one watt is one joule per second, total µmol/s divided by total J/s gives µmol/J. The result lists each group’s photon efficacy as well as the combined value, so two products can be compared by entering one in each row. Keep spectral band, operating setting and whole-system power boundaries compatible.
In an artificial comparison, one luminaire supplies 100 µmol/s at 50 W and another supplies 300 µmol/s at 100 W. Their individual photon efficacies are 2 and 3 µmol/J. Together they supply 400 µmol/s at 150 W = 2.67 µmol/J, rather than the simple average of 2.5. This comparison does not establish identical spatial distribution, spectrum or plant response. Actual receiving-plane PPFD still needs a measurement, a compatible optical model or an explicit photon delivery budget.