Use the height above the working plane
Room index describes the proportions of a rectangular space for a specified lighting method. It uses the separation between the luminaire reference and the working plane, rather than automatically using ceiling height. The NATSPEC lumen-method TECHnote, page 1, explains this geometry and its role in consulting utilisation data.
Let L and W be inside length and width in metres. If the source reference is at height H and the working plane at height P above the same level datum, their separation is h = H − P. The rectangular area is A = L × W, and:
Room index K = L × W ÷ [h × (L + W)].
K has no unit: both numerator and denominator have units of square metres. A larger K generally means a wider space relative to its source-to-plane height. It is not itself a percentage of light reaching the plane.
A common datum matters
Subtracting a source height measured from one floor level from a bench height measured from another gives the wrong separation. Suspended luminaires can also sit below the ceiling. Use the optical reference required by the applicable data, and identify the plane where the calculation is intended to apply.
Check an artificial rectangular example
Take a 10 m by 5 m room, with the luminaire reference 3 m and the working plane 1 m above a common datum. These are invented dimensions, not recommended installation heights.
- Area: 10 × 5 = 50.00 m².
- Source-to-plane separation: 3 − 1 = 2.00 m.
- Room index: 50 ÷ [2 × (10 + 5)] = 5/3, displayed as 1.6667.
Increasing both reference heights by the same amount leaves the separation and K unchanged. Doubling h while keeping length and width fixed halves K. The display rounds area and height to two decimal places and K to four; display rounding is not used in later calculations.
Room index does not choose a utilisation factor
A manufacturer table may need room index together with the applicable luminaire distribution and surface reflectances. Tables can use different flux and cavity conventions. A K value from this tool does not make a table appropriate, and interpolating or rounding into a table must follow that table’s method.
The lumen-method estimate requires an explicitly supplied UF and maintenance basis. Maintenance-factor composition separately combines declared maintenance components. For a coordinate sketch, equal-cell grid geometry uses the rectangle without claiming that its point spacing gives suitable lighting.